MAINTENANCE
Fault Diagnosis
If you require a Mira trained service engineer or agent, refer to section: ‘Customer
Services’.
Symptom Cause/Rectication
Only hot or cold water
from the mixer outlet.
Outlet temperature too
hot / too cold.
Inlets reversed (hot supply to cold supply). Rework inlet
pipework.
No hot or cold water reaching the mixer.
Check the lters for any blockage.
Installation conditions outside operating parameters, refer
to sections: ‘Specications’ and ‘Commissioning’.
Fluctuating or reduced
ow.
Check the shower handset, hose and filters for any
blockage.
Make sure that the maintained inlet pressures are
nominally balanced and sufficient, refer to section:
‘Specications’.
Make sure that the inlet temperature differentials are
sufcient, refer to section: ‘Specications’.
Air lock or partial blockage in the pipework.
Water leaking from
shower handset.
Normal for a short period after shut off.
Check that the pressures are not in excess of the
specications for the product.
Cartridge inlet seals damaged, renew.
Renew the ow cartridge.